Product name | PT Analyzer |
Type | PTA-2000C |
Function | Capacitive Voltage Transformer Tester |
Power Supply | ||
Voltage range | 200VAC~240VAC | |
Allowable voltage range | 180VAC~260VAC | |
Frequency | 50Hz/60Hz | |
Allowable frequency range | 45Hz~65Hz | |
Input power | Standby: 80VA Rated test power:600VA Peak power:1800VA | |
Output | ||
High voltage output | 0~3000VAC | |
Low voltage output | 0~120VAC,0~120VDC | |
Output current | 0~5A eff(15A peak) | |
Output power | 0~600VA eff(1500VA peak) | |
Electromagnetic voltage transformer(VT) | ||
Ratio test | Ratio:1~350 Voltage level: 0.6kV~35kV Typical accuracy:0.05% | |
Ratio:350~2450 Voltage level: 35kV~245kV Typical accuracy:0.05% | ||
Phase error test | Ratio:1~350 Voltage level : 0.6kV~35kV Typical accuracy:1min | |
Ratio:350~2450 Voltage level: 35kV~245kV Typical accuracy:2min | ||
Capacitor voltage transformer(CVT/CCVT) | ||
Ratio test | Ratio:300~8000 Voltage level: 30kV~800kV Typical accuracy:0.07% | |
Phase error test | Ratio:300~8000 Voltage level: 30kV~800kV Typical accuracy:2min | |
Coil resistance measurement | ||
Resolving power | 1mΩ | |
Typical accuracy | 0.05% | |
Guaranteed accuracy | 0.1% + 1mΩ | |
Load test | ||
Resolving power | 0.02VA | |
Typical accuracy | 0.05% | |
Guaranteed accuracy | 0.1% + 0.02VA | |
Size | ||
Volume | 700mm*590mm*350mm | |
Weight | 15kg ( No accessories included) | |
Environment condition | ||
Working temperature | -10℃~50℃ | |
Storage temperature | -25℃~70℃ | |
Relative humidity | 5%~95%,No condensation | |