Поделиться:
Месяц | Минимальная цена | Макс. стоимость |
---|---|---|
Sep-19-2025 | 0.98 $* | 0.68 $* |
Aug-19-2025 | 0.89 $* | 0.75 $* |
Jul-19-2025 | 0.4 $* | 0.40 $* |
Jun-19-2025 | 0.29 $* | 0.55 $* |
May-19-2025 | 0.64 $* | 0.1 $* |
Apr-19-2025 | 0.75 $* | 0.36 $* |
Mar-19-2025 | 0.68 $* | 0.97 $* |
Feb-19-2025 | 0.84 $* | 0.48 $* |
Jan-19-2025 | 0.43 $* | 0.73 $* |
Item | Automatic Tank Gauge | |
Usage | Used to display oil level, water level, oil storage volume and temperature | |
Design principle | Based on 32-bit ARM MCU | |
Screen size | 10 inch true color touch screen | |
Input voltage | AC220V | |
System working voltage | DC5V, DC24V | |
Operating ambient temperature range | - 40℃~+60℃ | |
Relative humidity | 45% - 75% | |
Atmospheric pressure | 86kpa ~ 106kpa | |
Measuring range | 200mm~7000mm | |
Output mode | RS-485 | |
Maximum communication distance | 1200m | |
Product power consumption | ≤40mA | |
Working temperature | -40℃ ~ +60℃ | |
Measurement accuracy | ±0.5mm | |
Repeated accuracy | ±0.2mm | |
Oil level resolution | 0.01mm | |
Water level resolution | 0.01mm | |
Temperature measuring point | 5 | |
Temperature sensor resolution | 0.0625℃ | |
Upper blind area | 90mm | |
Lowe blind area | 50mm | |
Explosion protection sign | [Ex ia Ga]IIA/Ex ia IIA T5 Ga | |
Related equipment | Zener safety barrier | |
Applicable medium | gasoline, kerosene, diesel, light oil, heavy oil, and crude alcohol mixture | |
Protection class | IP67 | |
Real time display of oil level, water level, temperature and volume | ||
It has the functions of automatically generating oil leakage test, alarm, oil inlet, oil storage, shift handover record, etc | ||
Large capacity data storage: up to 24 months of data stock | ||
The tank capacity is input point by point, and the measurement is more accurate | ||
It adopts 4-layer circuit design and is equipped with photoelectric isolator, lightning protection tube and TVs anti-interference device | ||
Make the system more safe, stable and reliable | ||
The system has multi-level password protection to make the data confidentiality more secure and reliable | ||
Support RS232 interface communication | ||
Support RS485 industrial bus | ||
The longest communication distance can reach 1200 meters |